Siemens SIMATIC S5-95F Manual page 111

Table of Contents

Advertisement

Expansion of Basic System with External I/Os
Example: Direct Control of Actuators (Type K)
Insert one module into slot n of subunit A and the other module into slot n+1 of subunit B, with
n being an even number between 0 and 30 (see section 6.2).
Set the selector switch of the module in subunit A to P (P output) and the selector switch of the
module in subunit B to M (M output) or vice versa.
Connect the 24 V DC supply voltage to terminals 1 and 2.
Wire the outputs with the actuators (as shown in Figure 5-14).
Parameterize the outputs in DB1.
M
P
M
L+
3
3
.0
4
4
5
5
.1
6
6
7
7
.2
8
8
9
9
.3
10
10
M
P
DIGITAL OUTPUT
4 x 24 V DC/2A
6ES5 450-8FA11
1
3
5
7
2
4
6
8
L+
M
Figure 5-14. Example for Connection of the External Digital Output Module with Direct P-M
5-16
9
Actuator A x.0
10
Actuator A x.1
Actuator A x.2
Actuator A x.3
DIGITAL OUTPUT
4 x 24 V DC/2A
6ES5 450-8FA11
1
Control of the Actuator
P
M
L+
M
3
3
.0
4
4
5
5
.1
6
6
7
7
.2
8
8
9
9
.3
10
10
M
P
3
5
7
9
2
4
6
8
10
EWA 4NEB 812 6210-02
S5-95F