Siemens SIMATIC S5-95F Manual page 307

Table of Contents

Advertisement

S5-95F
FB10 STL
NAME :SET CLOCK
DES
:WDAY
I/Q/D/B/T/C: I
DES
:DAY
I/Q/D/B/T/C: I
DES
:MON
I/Q/D/B/T/C: I
DES
:YEAR
I/Q/D/B/T/C: I
DES
:HOUR
I/Q/D/B/T/C: I
DES
:AMPM
I/Q/D/B/T/C: I
DES
:MIN
I/Q/D/B/T/C: I
DES
:SEC
I/Q/D/B/T/C: I
DES
:ERR
I/Q/D/B/T/C: Q
DES
:MODE
I/Q/D/B/T/C: I
:C
DB200
:AN
=MODE
:JU
=CONT
:SU
D
22.1
:A
F
20.0
:L
KT 200.0
:SE
T
10
WEIT :AN
F
20.0
:JC
=M001
:R
F
20.0
:
:
:L
=WDAY
:T
DR
4
:L
=DAY
:T
DL
5
:L
=MON
:T
DR
5
:L
=YEAR
:T
DL
6
:L
=HOUR
:ON
=AMPM
:ON
=MODE
:JC
=MORN
:L
KH 0080
:OW
MORN :T
DR
6
:L
=MIN
:T
DL
7
:L
=SEC
:T
DR
7
:SU
D
22.2
:
M001 :A
T
10
:BEC
EWA 4NEB 812 6210-02
SETTING THE CLOCK
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BI
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BI
BI/BY/W/D: BI
OPEN PARAMETER CONTROL DB
24H-MODE = 0, 12H-MODE = 1
CLOCK MODE STATUS WORD BIT 1
START MONITORING TIME
FLAG IS RESET IF SETTING
ALREADY READ INTO CLOCK
DATA AREA
CLOCK DATA AREA
STORE VALUE FOR WEEKDAY
VALUE FOR DAY
VALUE FOR MONTH
VALUE FOR YEAR
VALUE FOR HOUR
IF 12-HOUR MODE IS SET, AND
AM/PM BIT = 1 (AFTERNOON),
THE RELEVANT BIT IN
THE CLOCK DATA AREA
IS SET
VALUE FOR MINUTES
VALUE FOR SECONDS
TRANSFER SETTINGS
(STATUS WORD IS DW 22)
BEC, IF MONITORING
TIME NOT YET ELAPSED
The Integral Real-Time Clock
Explanation
10-11