Panasonic FP-E Programming Manual page 1141

Fp series
Table of Contents

Advertisement

WR904 FP0R
Relay
No.
TOOL port
R9040
operation mode
flag
COM port PLC
R9041
link flag
R9042
Not used
R9043
Not used
COM port
SEND/RECV
R9044
instruction
execution flag
COM port
SEND/RECV
R9045
instruction
execution end
flag
R9046
Not used
R9047
Not used
R9048
Not used
R9049
Not used
R904A
Not used
R904B
Not used
R904C
Not used
to R904F
A: Available, N/A: Not available
Note) R9040 to R904F can be changed during 1 scan.
WR905 FP0R
Relay
Name
No.
MEWNET-W0
PLC link
R9050
transmission
error flag
R9051 to
Not used
R905F
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Turns on when the general-purpose communication function is being
-
used
Goes off when the computer link function is being used.
-
Turn on while the PLC link function is used.
Monitors whether the F145 (SEND) or F146 (RECV) instructions can
be executed or not.
Off: None of the above mentioned instructions can be executed.
(During executing the instruction)
On: One of the above mentioned instructions can be executed.
Monitors if an abnormality has been detected during the execution of
the F145 (SEND) or F146 (RECV) instructions as follows:
Off: No abonormality detected.
On: An abnormality detected. (communication error)
End code: DT90124
When using MEWNET-W0
Turns on when a transmission error occurs at PLC link.
-
Turns on when there is an error in the PLC link area settings.
-
Description
Description
5-53