FP0
Add-
Item
ress
High-
speed
counter
Input
401
setting
mode
settings
(X3 to X5)
Note1) If the operation mode is set to 2-phase, individual, or direction differentiation, the setting for CH3
is invalid.
Note2) If reset input settings overlap, the setting of CH3 takes precedence.
Note3) If system register 400 to 403 have been set simultaneously for the same input relay, the following
precedence order is effective: [High-speed counter] '[Pulse catch]' [Interrupt input].
5-10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Default
Name
value
Do not
set X3
as high-
speed
counter.
Do not
set X4
as high-
speed
counter.
Setting
by
progra-
mming
tool
soft-
ware
H0
Descriptions
Do not set X3 as high-speed counter.
2-phase input (X3, X4)
2-phase input (X3, X4),
Reset input (X5)
Incremental input (X3)
Incremental input (X3), Reset input (X5)
Decremental input (X3)
Decremental input (X3),
CH2
Reset input (X5)
Individual input (X3, X4)
Individual input (X3, X4),
Reset input (X5)
Direction decision (X3, X4)
Direction decision (X3, X4),
Reset input (X5)
Do not set X4 as high-speed counter.
Incremental input (X4)
Incremental input (X4), Reset input (X5)
CH3
Decremental input (X4)
Decremental input (X4), Reset input (X5)
CH2/
CH3