Mitsubishi Q01CPU User Manual page 545

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

12
TROUBLESHOOTING
Error
Code
Error Contents and Cause
(SD0)
• The number of CPU modules
7032
mounted in a multiple CPU system is
wrong.
The CPU module has been mounted on
7035
the inapplicable slot.
The host CPU No. set by the multiple
CPU setting and the host CPU No.
7036
determined by the mounting position of
the CPU module are not the same.
The error of stored file (enabled
8031
parameter file) is detected.
9000
Annunciator (F) was set ON
9010
Error detected by the CHK instruction.
Storage of data onto ROM was
completed normally in automatic write
9020
to standard ROM.
(BOOT LED also flickers.)
In the multiple CPU system, an error
occurred in the CPU module other than
10000
the Process CPU/High Performance
model QCPU.
*3
The Universal model QCPU except the Q02UCPU.
*4
The module whose first 5 digits of serial No. is 09082 or later.
*5
Abbreviation for "MELSEC-Q series-compatible PC CPU module bus interface driver software package"
Corrective Action
Configure a system so that the number
of mountable modules of each CPU
module does not exceed the maximum
number of mountable modules specified
in the specification.
Mount the CPU module on the
applicable slot.
• Mount the mounting slot of the CPU
module correctly.
• Correct the host CPU No. set by the
multiple CPU setting to the CPU No.
determined by the mounting position
of the CPU module.
Write the file shown as SD17 to SD22 of
individual information to the drive shown
as SD16(L) of individual information,
and turn ON from OFF the power supply
of the CPU module or cancel the reset.
If the same error is displayed again, the
CPU module has hardware failure.
Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.
Read the individual information of the
error using the peripheral device, and
check the program corresponding to the
numerical value (annunciator number).
Read the individual information of the
error using the peripheral device, and
check the program corresponding to the
numerical value (error number) there.
Use the DIP switches to set the valid
parameter drive to the standard ROM.
Then, switch power on again, and
perform boot operation from the
standard ROM.
Check the details of the generated error
by connecting to the corresponding
CPU module using GX Developer.
12.3 Error Code List
12.3.9 Error code list (7000 to 10000)
9
Corresponding
CPU
*1
Q00/Q01
10
QnU
Q00J/Q00/
*1
Q01
QnPRH
QnU
11
*3
QnU
12
QnU
QnA
Qn(H)
QnPH
QnPRH
*1
Qn(H)
QnPH
QnPRH
*1
Qn(H)
QnPH
12
- 221

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents