Flowchart For When Output Load Of Output Module Does Not Turn On - Mitsubishi Q01CPU User Manual

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

12
TROUBLESHOOTING

12.2.14 Flowchart for when output load of output module does not turn on

The following shows the flowchart for when the output load of the output module does not
turn on during programmable controller operation.
The output load has not turned on.
Is the operation
indicator of output module
turned on?
YES
Is voltage for the
power supply load
added?
YES
What is the voltage
among the various
output COM terminals of the
output module?
The rated voltage
is supplied.
Output module failure
Replace the output module.
Confirm rush current that flows to the
load when the maximum number of
outputs turns on simultaneously.
OK
Diagram 12.11 Flowchart for when output load of output module does not turn on
Check output conditions with the
NO
monitor mode of the GX
Developer.
NO
indicator of input
module turned on?
0V
Set the GX Developer in the
monitor mode and check that the
input signal is OFF.
Check the power supply load
wire and recover the power
supply.
Check the load wire and load, and
recover the power supply.
Change the output relay number and
NG
let the load maximum simultaneous
on current to within the specification.
POINT
For the troublet in which input signal to the input module does not turn off,
troubleshoot referring to Section 12.5 Examples of I/O Modules Troubleshooting.
12.2.14 Flowchart for when output load of output module does not turn on
Is the operation
Off
On
12.2 Troubleshooting
Voltage measurement among
the modules input and COM
terminals.
0V
(Monitor signal off)
Check the external wiring and
external input devices.
Please consult your local Mitsubishi
service center or representative,
explaining a detailed description of
the problem.