Mitsubishi Q01CPU User Manual page 473

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

12
TROUBLESHOOTING
Error
Code
Error Contents and Cause
(SD0)
Since the number of points of the B/W
device set in [Device] of the PLC
parameter is lower than the number of
B/W refresh device points shown in the
following table when parameters of the
MELSECNET/H are not set, the refresh
between the CPU module and the
MELSECNET/H cannot be performed.
3101
Refresh
No. of refresh device
device
points of B device
8192 points
1
(8192 points
module)
8192 points
No. of
2
(4096 points
mountable
modules)
network
6144 points
modules
3
(2048 points
modules)
8192 points
(2048 points
4
modules)
A CC-Link IE controller network
parameter error was detected.
• The network module detected a
network parameter error.
• A MELSECNET/H network parameter
error was detected.
The station No. specified in pairing
setting are not correct.
• The stations are not numbered
consecutively.
• Pairing setting has not been made for
the CPU module at the normal
3102
station.
The CC-Link IE controller network
module whose first 5 digits of serial No.
is "09041" or earlier is mounted.
Paring setting in CC-Link IE controller
network modules installed in CPUs
except for Redundant CPUs was
performed.
• LB/LW own station send range at LB/
LW4000 or later was set.
• LB/LW setting (2) was performed.
*4
The module whose first 5 digits of serial No. is 04012 or later.
*5
The module whose first 5 digits of serial No. is 07032 or later.
*6
The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*7
The module whose first 5 digits of serial No. is 09012 or later.
*8
The Universal model QCPU except the Q02UCPU.
*9
The module whose first 5 digits of serial No. is 10042 or later.
Set the refresh parameter of the
MELSECNET/H in accordance with the
number of points of B/W devices set in
No. of refresh device
points of W device
[Device] of the PLC parameter.
8192 points
1
(8192 points
1
module)
8192 points
2
(4096 points
2
modules)
6144 points
3
(2048 points
3
modules)
8192 points
4
(2048 points
4
modules)
• Correct and write the network
parameters.
• If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
Refer to the troubleshooting of the
network module, and if the error is due
to incorrect pairing setting, reexamine
the pairing setting of the network
parameter.
Mount the CC-Link IE controller network
module whose first 5 digits of serial No.
is "09042" or later.
Examine the paring setting for the
network parameter in the control staion.
Examine the network range
assignments for the network parameter
in the control station.
Corrective Action
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
9
Corresponding
CPU
10
*6
Qn(H)
*6
QnPH
*6
QnPRH
11
QnU
12
*6
Qn(H)
QnU
QnPRH
QnU
Q00J/Q00/Q01
*9
Qn(H)
*9
QnPH
*9
QnU
Q00J/Q00/Q01
12
- 149

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents