EMC AND LOW VOLTAGE DIRECTIVES

9.1.4 Power Supply Module and Q00JCPU's Power Supply Part

Always ground the LG and FG terminals after short-circuiting them.

9.1.5 When Using MELSEC-A Series Modules

The following describes the case where the MELSEC-A series module is used, using the
QA1S6 B, QA6 B, and QA6ADP+A5 B/A6 B as the extension base unit.
(1) Cable
9
- 8
9.1 Requirements for Conformance to EMC Directive
9.1.4 Power Supply Module and Q00JCPU's Power Supply Part
(a) Grounding of the shield of the shielded cable
• Ground the shield of the shielded cable as near the unit as possible taking
care so that the grounded cables are not induced electromagnetically by the
cable to be earthed.
• Ground the shield of the shielded cable, which was exposed by removing a
part of the outer sheath, to the control panel as a large area as possible.
A clamp may also be used as shown in Diagram 9.12.
However, mask the part inside the control panel, with which the clamp comes
in contact, when coating.
Shield section
Diagram 9.11 Part to be exposed
Note) The method of grounding by soldering a wire onto the shield section of the
shielded cable as shown in Diagram 9.13 is not recommended. The high
frequency impedance will increase and the shield will be ineffective.
Diagram 9.13 Shield grounding (Incorrect example)
Paint mask
Diagram 9.12 Shield grounding (Correct example)
Shield cable
Wire
Solderless terminal, crimp contact
Screw
Clamp fitting
Shield cable