12
TROUBLESHOOTING
Error
Code
Error Contents and Cause
(SD0)
In PLC parameter I/O allocation
settings, a special function module was
2100
allocated to a location reserved for an I/
O module. Or, the opposite has
happened.
13 or more A-series special function
modules (except for the A1SI61) that
can initiate an interrupt to the CPU
module have been installed.
2101
13 or more special function modules
(not counting the A(1S)I61) capable of
sending an interrupt to the CPU module
have been installed.
Seven or more A1SD51S have been
installed.
2102
Seven or more serial communication
modules (excludes A (1S) J71QC24)
have been installed.
*3
The function version is B or later.
*4
The function version is A.
*5
The module whose first 5 digits of serial No. is 04101 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.
*8
This applies to the QnUDE(H)CPU.
*9
The module whose first 5 digits of serial No. is 10042 or later.
Corrective Action
Reset the PLC parameter I/O allocation
setting to conform with the actual status
of the special function modules.
Reduce the A series special function
modules (except the A1SI61) that can
make an interrupt start to the CPU
module to 12 or less.
Keep the number of special function
modules that can initiate an interrupt
(with the exception of the A(1S)I61
module) to 12 or fewer.
Keep the number of A1SD51S to six or
fewer.
Keep the number of serial
communication modules (excludes
A(1S)J71QU24) installed to six or fewer.
12.3 Error Code List
12.3.4 Error code list (2000 to 2999)
9
Corresponding
CPU
QnA
10
Qn(H)
11
QnA
Qn(H)
12
QnA
12
- 97

Hide quick links: