5.2.3 Precaution when connecting the uninterruptive power supply

Be sure of the following terms when connecting the Q series CPU module system to the
uninterruptive power supply (hereinafter referred to as UPS):
Use the online UPS or line interactive UPS with a voltage distortion rate of 5% or less.
For the off-line system UPS, use Mitsubishi Electric's F Series UPS (serial number P or
later) (Ex.: FW-F10-0.3K/0.5K).
Do not use any off-line system UPS other than the F series mentioned above.

5.2.4 Cautions on power supply capacity

The Q64RP and Q64P automatically recognize the rated input voltage waveform to switch
the input voltage between 100VAC and 200VAC.
Select the power supply for the Q64RP/Q64P power supply module, considering the
power supply capacity. (Reference: At least twice as much as the current consumption)
If the power supply of insufficient capacity is applied, the power supply module might fail
when 200VAC power is supplied.
5
- 24
5.2 Specifications
5.2.3 Precaution when connecting the uninterruptive power supply
A series power supply
module A61P, A61PN, A62P,
A63P
Diagram 5.5 Modules and peripheral device that are powered
Select the power supply module also in consideration of the current consumption of
the peripheral devices connected to the special function module.
For example, when the AD75TU is connected to the AD75P1-S3, the current
consumption of the AD75TU must also be taken into account.
Base unit QA65B,
QA68B
I/O module AX10,
AY10, etc.
Special function module
AD61,AD75P1-S3, etc.
by power supply module
Peripheral
device
AD75TU