Instructions For Mounting The Base Unit - Mitsubishi Q01CPU User Manual

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

10
LOADING AND INSTALLATION

10.3.2 Instructions for mounting the base unit

When mounting the programmable controller to an enclosure or similar, fully consider its
operability, maintainability and environmental resistance.
(1) Module mounting position
4
5mm (0.20 inch) or more
2, 6
10
- 20
10.3 Module Installation
10.3.2 Instructions for mounting the base unit
Keep the clearances shown in Diagram 10.18 or Diagram 10.19 between the top/
bottom faces of the module and other structures or parts to ensure good ventilation
and facilitate module replacement.
(a) In case of main base unit or extension base unit
Indicates the panel top, wiring duct or any
part position.
5, 6
5mm (0.20 inch) or more 6
* 1: For wiring duct with 50mm (1.97 inch) or less height.
40mm (1.58 inch) or more for other cases.
* 2: 20mm (0.79 inch) or more when the adjacent module is not removed and the extension cable is
connected.
* 3: 80mm (3.15 inch) or more for the connector type. 140mm (5.51 inch) or more for installing a
tracking cable when using a Redundant CPU. 80mm (3.15 inch) or more for installing the Q8BAT
cable when using the Q8BAT.
* 4: 45mm (1.77 inch) or more when the Q7BAT is mounted.
* 5: 30mm (1.18 inch) or more from the top and bottom of the Q8BAT when the Q8BAT is mounted.
* 6: 5mm (0.20 inch) or more from the right and left of the Q8BAT when the Q8BAT is mounted.
Diagram 10.18 Module mounting position
30mm(1.18 inch)
or more
1, 5
Panel
30mm(1.18 inch)
or more
4, 5
Programmable
controller
Door
20mm
(0.79 inch)
or more
3