Mitsubishi Q01CPU User Manual page 415

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

12
TROUBLESHOOTING
Error
Code
Error Contents and Cause
(SD0)
• More than applicable number of
extension base units have been used.
2010
• When a GOT was bus-connected, the
CPU module was reset while the
power of the GOT was OFF.
The QA1S6 B, QA6 B or
2011
QA6ADP+A5 B/A6 B was used as
the base unit.
*3
The function version is B or later.
*4
The function version is A.
*5
The module whose first 5 digits of serial No. is 04101 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.
*8
This applies to the QnUDE(H)CPU.
*9
The module whose first 5 digits of serial No. is 10042 or later.
Corrective Action
• Use the allowable number of
extension base units or less.
• Power on the Progammable
Controller and GOT again.
Do not use the QA1S6 B, QA6 B or
QA6ADP+A5 B/A6 B as the base
unit.
12.3 Error Code List
12.3.4 Error code list (2000 to 2999)
9
Corresponding
CPU
Q00J/Q00/
*3
Q01
10
QnPRH
Q02U
Q00J/Q00/
*3
Q01
QnPRH
QnU
11
12
12
- 91

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents