EMC AND LOW VOLTAGE DIRECTIVES
(4) Positioning module, channel-isolated pulse input module
(5) Temperature control module
9
- 6
9.1 Requirements for Conformance to EMC Directive
9.1.3 Cables
Use shielded cables for the external wiring, and ground the shields of the external
wiring cables to the control box with the AD75CK cable clamp (Mitsubishi Electric
make).
(Ground the shields 20 to 30cm away from the module.)
Inside control box
20 to 30cm
(7.87 to 11.81 inch)
AD75CK
Diagram 9.8 AD75CK cable clamp mounting position
The AD75CK allows up to four cables to be grounded if the outside diameter of the
shielded cable is about 7mm.
Use shielded cables for the external wiring, and ground the shields of the external
wiring cables to the control box with the AD75CK cable clamp (Mitsubishi Electric
make).
(Ground the shields 20 to 30cm away from the module.)
Inside control box
20 to 30cm
(7.87 to 11.81 inch)
AD75CK
Diagram 9.9 AD75CK cable clamp mounting position
The AD75CK allows up to four cables to be grounded if the outside diameter of the
shielded cable is about 7mm.
The required number of AD75CKs is indicated in Table9.2. (When cables of 7mm
outside diameter are used for all wiring.)