Mitsubishi Q01CPU User Manual page 463

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

12
TROUBLESHOOTING
Error
Code
Error Contents and Cause
(SD0)
• In a multiple CPU system, the online
module change parameter (multiple
CPU system parameter) settings
differ from those of the reference
CPU.
3014
• In a multiple CPU system, the online
module change setting is enabled
although the CPU module mounted
does not support online module
chang parameter.
In a multiple CPU system configuration,
3015
the CPU verified is different from the
one set in the parameter setting.
The CPU module incompatible with
multiple CPU synchronized boot-up is
3016
set as the target for the synchronized
boot-up in the [Multiple CPU
synchronous startup setting].
3040
The parameter file is damaged.
Parameter file of intelligent function
3041
module is damaged.
*4
The module whose first 5 digits of serial No. is 04012 or later.
*5
The module whose first 5 digits of serial No. is 07032 or later.
*6
The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*7
The module whose first 5 digits of serial No. is 09012 or later.
*8
The Universal model QCPU except the Q02UCPU.
*9
The module whose first 5 digits of serial No. is 10042 or later.
Corrective Action
• Match the online module change
parameter with that of the reference
CPU.
• If the CPU module that does not
support online module change is
mounted, replace it with the CPU
module that supports online module
change.
Read the individual information of the
error using the peripheral device, check
the parameter item corresponding to the
numerical value (parameter No./CPU
No.) and parameter of target CPU, and
correct them.
Delete the CPU module incompatible
with multiple CPU synchronized boot-up
from the setting.
With GX Developer, write [PLC
parameter/Network parameter/Remote
password] to a valid drive then reload
the power supply for system and/or
reset the CPU module. If the same
error occurs, it is thought to be
hardware error. (Contact your local
Mitsubishi representative.)
With GX Developer, write [Intelligent
function module parameter] to a valid
drive to write the parameters then
reload the power supply for system and/
or reset the CPU module. If the same
error occurs, it is thought to be a
hardware error. (Contact your local
Mitsubishi representative.)
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
9
Corresponding
CPU
10
Qn(H)
QnPH
*8
QnU
11
QnU
12
*8
QnU
*5
Qn(H)
*5
QnPH
*5
QnPRH
*5
Qn(H)
*5
QnPH
*5
QnPRH
12
- 139

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents