8.5.3

Digital input characteristics

8.5.4

Digital output characteristics

DANGER
The plug connectors for the inputs and the outputs must not be connected or
disconnected under load.
Input types
Number of inputs
Status display by LED
Electrical isolation
Reverse voltage protection
Plug-in grid
Tab. 8-6:
Digital input characteristics
Output types
Semiconductor outputs, non-saving; protected, with automatic
restart, current-carrying
Number of outputs
8
Status display by
Green
LED
Electrical isolation
Yes (to logic supply)
Reverse voltage
Only guaranteed without load connection
protection
Defect of the component caused by
Polarity reversal with simultaneous short circuit of the
output lines
Polarity reversal with simultaneous connection of exter‐
nally polarized suppressor diodes at the output lines
Applying an external voltage > U
Output voltage
Nominal value
24 V
Rated output cur‐
rent
0.2 A
Nominal value:
0.2 A general purpose
UL rating:
5W Tungsten
Simultaneity factor
100 %
Plug-in grid
3.5 (Weidmüller terminal)
Tab. 8-7:
Digital output characteristics
Bosch Rexroth AG
Dangerous movements caused by plugging
or unplugging plug connectors under load!
Type 1 acc. to EN 61131-2
16
Green
Yes (to logic supply)
yes
3.5 (Weidmüller terminal)
Q
43/69
Interfaces