Output Ssm-Value Vs. Clock State - Symmetricom TimeProvider 5000 User Manual

Ieee 1588 grand master clock / ntp server
Hide thumbs Also See for TimeProvider 5000:
Table of Contents

Advertisement

Chapter 4 Provisioning
Provisioning the Programmable E1/T1 Outputs
If the output frame type supports SSM and SSM is enabled for the output port, then
the output signal will contain the system SSM value.
SSM value based on the clock state of the TP5000.
Table 4-18. Output SSM-value vs. Clock State
Clock State
Warm-up
Free-run
Fast-lock
Normal
Bridging
Holdover
2048kHz Frame Type
To provision Port 1 as an output port with a frametype of 2048kHz, CRC disabled,
SSM disabled, and to enable the port:
1. Login at the Admin or Config-user level.
2. Type
set io port1 output
3. Type
set output frametype port1 freq2048khz
4. Type
set output crc port1 disable
5. Type
set output ssm port1 disable
6. Type
set output state port1 enable
CCS Frame Type
To provision Port 2 as an output port with a frametype of CCS, CRC enabled, SSM
enabled, SSM-bit of 4, and to enable the port:
1. Login at the Admin or Config-user level.
2. Type
set io port2 output
3. Type
set output frametype port2 ccs
326 TimeProvider 5000 User's Guide
Output SSM-value
PQL=9 - Do not use for Sync
(DUS)
PQL of oscillator
PQL of oscillator
PQL of reference
Last PQL of reference
PQL of oscillator
and press Enter.
and press Enter.
Table 4-18
shows the output
and press Enter.
and press Enter.
and press Enter.
and press Enter.
and press Enter.