2. OPERATION
MEMO
RANDUM
Note:8. When starting operation, always connect the external emergency stop
(EM1) and SG. (Normally closed contacts) By setting 0001 in parameter
No. 23, the external emergency stop signal can be made invalid.
9. Applies to the servo motor with electromagnetic brake.
10. The personal computer and monitor outputs 1, 2 cannot be connected
together.
11. Total length of the bus cables used should be within 30m. To improve noise
immunity, it is recommended to use a cable clamp or data line filters (3 or 4
pcs. connected in series) near the connector lead-out.
12. The wiring for the second and subsequent axes is omitted.
13. Up to 8 axes may be connected in the same system.
14. Always fit the termination connector (MR-A-TM) to CN1B of the last servo
amplifier.
15. The bus cables used depend on the servo system controller to be
connected.
16. The connection method depends on the servo motor series. Refer to
Section 3-2-2.
17. A single-phase 230V power supply may be used with the servo amplifier of
MR-J2-70B or less. Connect the power supply to L1 and L2 terminals and
leave L3 open.