6. OPTION AND AUXILIARY EQUIPMENT
(3) Connection of the regenerative brake option
When using the regenerative brake option, always remove wiring from across P-D and install the
regenerative brake option across P-C. Set parameter No.2 according to the option to be used. The
regenerative brake option will generate heat of about 100 . Fully examine heat dissipation,
installation position, used cables, etc. before installing the option. For wiring, use fire-retarding cables
and keep them clear of the regenerative brake option body. Always use twisted cables of max. 5m
length for connection with the servo amplifier.
Parameter No. 2
0
0
Servo amplifier
D
P
C
5m (16.4 ft) max.
Note: Make up a sequence which will switch off the magnetic contactor
(MC) when abnormal heating occurs.
Selection of regenerative
brake option
00:Not used.
05:MR-RB 32
08:MR-RB 30
09:MR-RB 50
10:MR-RB 032
11:MR-RB 12
CAUTION
Regenerative brake option
P
C
G3
(Note)
G4
Always remove the
lead from across P-D.
G3 G4: Thermal protector terminals.
Abnormal heating will dis-
connect G3-G4.
6 - 3