Error Log
Time Information
Note
8-2-2

Error Codes

Error
Contents
code
0001
PLC watchdog timer error
Hex
0002
PLC service monitor error
Hex
0004
CPU Bus Unit ID number error
Hex
0006
CPU Unit error
Hex
000E
I/O Bus error
Hex
000F
PLC initialization error
Hex
0010
PLC Setup exceeds capacity
Hex
0011
PLC initialization error
Hex
(Time out)
138
The time is recorded in BCD with one byte each for the year (the rightmost
two digits), month, day, hour, seconds, and minutes of the time the error
occurred.
(1) The PLC's time information can be read and used in the SYSMAC LINK
Unit. When the time cannot be read from the PLC, all error log times will
be set to 0. This can occur for PLC startup errors, unit number errors,
CPU Unit errors, or PLC model errors. When error logs without times are
read from the CX-Net, they will be dated 0 s, 0 min, 0 hr, 0 day, 0 month,
2000.
(2) When replacing the battery for CS-series PLCs, it will be necessary to
switch the power supply ON and reset the internal clock. If the internal
clock is not reset, time information in the error log will not be recorded cor-
rectly.
(3) The time information will be all zeros for CQM1H-series PLCs unless a
Memory Cassette with a clock is mounted in the CPU Unit. The time in-
formation will be all zeros in the year 2000 if it is read from Support Soft-
ware.
The following table lists the error codes (in 4-digit hexadecimal) and the con-
tents of the errors.
Detail code
1st byte
2nd byte
00 Hex
00 Hex
Monitor time (unit: ms)
00 Hex
00 Hex
Bit 11: No relevant Unit in I/
O table.
Bit 12: Hardware test unit
number recognized.
Bit 13: Incorrect unit num-
ber.
Bit 14: Duplicated unit num-
ber.
00 Hex fixed
00 Hex fixed Check the operating environ-
Correction
Replace PLC's CPU Unit.
Check operating environment. Yes
Check I/O Connecting
Cables.
Check the Unit number set-
tings. Recreate the I/O table.
ment.
Check the operating environ-
ment.
Reduce the number of CPU
Bus Units mounted on each
CPU Unit by one.
Check the operating environ-
ment.
Section 8-2
Written to
EEPROM
Yes
Yes
Yes
Yes
Yes
Yes
Yes