Equipment

Selections listed in this section are dependent on system hardware
configuration. Not all options will be available.
NOTE - When changing the default settings for any parameter, there is a
possibility that it will affect the settings for another parameter. If this happens, a
pop-up message will be displayed listing the other affected parameters and
their new automatically set values.
display
equipment name
alerts
Changing Temperature Control Mode
filter 1 timer selection
has affected the following parameters:
filter 2 timer selection
uv bulb timer selection
Temperature Control
continues blower cmf
zone 1
Wall Insulation
zone 2
zone 3
The following is a complete list of all possible parameters under System.
Parameters actually available are dependent on the Lennox communicating
equipment type detected and non-communicating equipment added.
This screen provides information concerning language supported, equipment
type name, control software revision, model, control mode number, control
serial number, control hardware revision, protocol revision number, device
product level, 24VAC average power consumption, 24VAC peak power
consumption, compatible devices list, application code memory size and
micro-controller part number.
Equipment Name
A unique name can be assigned to this component. Name can be up to 29
characters. Name can consist of letters, numbers, special characters and
spaces. Default name is Subnet Controller.
Temp Reading Calibration
Range is -5.0 to 5.0°F. Default is 0.0°F
warning
name
new value
1
Mode
2
ok

Smart Hub

About
If it is determine that the actual temperature being detected at the thermostat
is off based on independent readings using other ambient temperature reading
devices, the display can be adjusted using this setting.
Humidity Reading Calibration
Range is -10.0 to 10.0%. Default is 0.0%
If it is determine that the actual humidity percentage being detected at the
thermostat is off based on independent readings using other humidity reading
devices, the display can be adjusted using this setting.
Smooth Setback Recovery
When enabled, smooth set back begins recovery up to two hours before the
programmed time so that the programmed temperature is reached at the
corresponding programmed event time. Assume 12°F per hour for first-stage
gas/electric heating and 6°F per hour for first-stage compressor based heating
or cooling. With Smooth Set Back disabled, the system will start a recovery at
the programmed time. Options are enabled or disabled. Default is enabled.
Gas Heating Activation Temp Difference
Range is 0.5 to 10°F. Default is 1.5°F. Adjustments are in increments of 0.5°F.
When the system is dual-fuel and steady state while operating at full HP
demand, this is the amount of °F below the set point that is allowed before
allowing to switch to gas heat.
Electric Heat Control Mode
(SL18XC, SL18XP, XC17, XP17, XC21 and XP21 Only)
In heat pump applications, the electric heat is staged to provide supplemental
heat to meet desired comfort levels. When the electric heat section is used in
applications that do not have a heat pump, the elements are staged to limit heat
so that it meets heating demands only. Options are Standard and EvenHeat.
Default is Standard.
EvenHeat Discharge Temp
When in EvenHeat Control Mode, the iComfort
sections to maintain a constant discharge air temperature. The system must
have a discharge sensor connected to the system to show this parameter.
NOTE - Not selectable on XC/XP25 applications. Electric heat elements will be
staged on by the demand of the iComfort
Range is 85 to 130ºF. Default is 85ºF. Adjustments can be made in increments
of 15ºF.
Gas Heat Control Mode (SLP98 only)
Options are Staged, Load Tracking Variable Capacity and Variable Capacity.
Default is Staged.
22
®
S30 will stage the electric heat
®
S30.