Response Wait Time Settings [Par4→ Rsw.t]; Enable/Disable Communication Write[Par4→ Comw] - Autonics TK4S User Manual

Standard type temp controller tk series
Hide thumbs Also See for TK4S:
Table of Contents

Advertisement

6.6.5
Response Wait time Settings [PAR4→ RSW.T]
Set a standby time to mitigate communication errors when communicating with a slow
master device (PC, PLC, etc.). Once a standby time is set, the controller will respond after
the defined standby time.
Setting
Group
PAR4
6.6.6
Enable/disable Communication Write[PAR4→ COMW]
This feature can change parameter settings stored in memory through communication
with PC, GP, PLC, etc., in order to permit or prohibit writing.
Setting
Group
PAR4
© Copyright Reserved Autonics Co., Ltd.
Parameter
RSW.T
Shorter standby times can cause communication errors in the master
device.
Setting
Parameter set/change enable via communication.
EN.A
Prohibit parameter setting or modification via communication.
DIS.A
Parameter
COMW
Reading parameter settings is always permitted.
6 Parameter Settings and Functions
Setting Range
05 to 99
Description
Setting Range
EN.A / DIS.A
Factory
Unit
Default
ms
20
Factory
Unit
Default
-
EN.A
95