6.7.5
Error Features
The controller diagnoses input signals for errors and displays messages accordingly.
These messages inform the user of device problems.
6.7.5.1
MV Settings upon Sensor Break Error (Open) [PAR5 → ER.MV]
Setting
Group
PAR5
© Copyright Reserved Autonics Co., Ltd.
Message
Flashes at 0.5-second intervals if the input value is above the input range.
HHHH
→ Automatically deactivates and returns to normal operation if the input
value returns to the input range.
Flashes at 0.5-second intervals if the input value is below the input range.
LLLL
→ Automatically deactivates and returns to normal operation if the input
value returns to the input range.
Flashes at 0.5-second intervals in the event of an input disconnection.
OPEN
→ Automatically deactivates and returns to normal operation if input
reconnects.
Flashes twice at 0.5-second intervals in the event of an operation error
ERR
and returns to the previous screen.
When in heating control mode and powered on, or standard control
state, output is 0% if HHHH is displayed and 100% if LLLL is
displayed.
When in cooling control and powered on (or standard control state),
output is 100% if HHHH is displayed and 0% if LLLL is displayed.
When in heating and cooling control and powered on or standard
control state, heating output is 0% and cooling output 100% if HHHH is
displayed, and heating output is 100% and cooling output 0% if LLLL
is displayed.
In the event of a sensor open error you can set control output value to predefined MV
instead of ON/OFF control or PID control.
Ignores MV by ON/OFF control or PID control, and sends out a control value based
on the defined MV.
Parameter
Standard
Control
ER.MV
Heating
Cooling
Control
Description
Setting Range
ON/OFF
000.0 (OFF)/100.0 (ON)
Control
PID
Control
ON/OFF
Control
/000.0 (OFF)/100.0 (Heating On)
and
PID
`00.0 (Cooling) to 100.0
Control
6 Parameter Settings and Functions
000.0 to 100.0
`00.0 (Cooling On)
(Heating)
Factory
Unit
Default
000.0
000.0
%
000.0
000.0
103