Analog Input/Scale Settings - Autonics TK4S User Manual

Standard type temp controller tk series
Hide thumbs Also See for TK4S:
Table of Contents

Advertisement

6 Parameter Settings and Functions
6.1.4

Analog Input/Scale Settings

6.1.4.1
Low-limit Input Value Settings [PAR3 → L-RG]
You can set the low limit input values for actual use within the analog input range.
Setting
Group
PAR3
6.1.4.2
High-limit Value Settings [PAR3 → H -RG]
You can set high limit input values for actual use within the analog input range.
Setting
Group
PAR3
6.1.4.3
Decimal Point Position Settings [PAR3 → DOT]
You can set the decimal point positions for PV (Present Value) and SV (Setting Value)
within high and low limit scale values.
Setting
Group
PAR3
52
With analog input selected, you can set the analog input range (high/low limit input
values) and the display scale (high/low limit scale values) within the designated input
range.
The decimal point positions will remain fixed when configuring the upper/lower limit
input values. You can change the input values at AV1: 00.00, AV2/AV3: 0.000, AMV1:
000.0, and AMA1/ AMA2: 00.00 decimal points.
If the upper and lower limit scale settings are identical, an ERR message flashes twice
and setting mode is displayed.
This parameter will not be displayed if temperature sensor input is
selected.
Parameter
Minimum Temperature Range to High-limit
L-RG
Input Value (H-RG) - F.S. 10%
Parameter
Low-limit Input Value (L-RG) + F.S. 10% to
H-RG
Maximum Temperature Range
Parameter
DOT
Setting Range
Setting Range
Setting Range
0 / 0.0/ 0.00 / 0.000
© Copyright Reserved Autonics Co., Ltd.
Factory
Unit
Default
-
00.00
Factory
Unit
Default
-
10.00
Factory
Unit
Default
-
0.0