Run/Stop [Par1 → R-S] - Autonics TK4S User Manual

Standard type temp controller tk series
Hide thumbs Also See for TK4S:
Table of Contents

Advertisement

6 Parameter Settings and Functions
6.7.2
Run/Stop [PAR1 → R-S]
Setting Group
6.7.2.1
Stop Control Output Settings [PAR5 → ST.MV]
This parameter sets the control output value when in the stop state. With ON/OFF control,
select between 100.0 (ON) and 000.0 (OFF). With PID control, the user can adjust the
MV between 000.0 and 100.0.
Setting
Group
PAR5
98
Users may run or stop control output by force while in Run mode.
The stop command stops control output. Auxiliary output, however, is not affected by
the command.
This feature can be enabled by configuring parameters. In addition, the front panel's
digital input keys (▼ and ▲) and digital input terminals (DI-1 and DI-2) can be assigned
to the run/stop feature.
Setting
Forced control output run in Stop mode.
RUN
Forced control output stop in Run mode.
STOP
Parameter
PAR1
R-S
With stop enabled, the front panel's SV display indicates STOP.
You can change the setting when in the stop state. The stop status will
remain in effect after shutting down the controller and powering it back
on.
When stop is in effect, STOP MV will be output. In case of a sensor
break occuring while in STOP, STOP MV is output.
The run/stop setting remains in effect after turning power back on.
If the Digital Input (, ) feature has been set for RUN/STOP,
RUN/STOP feature by modifying front keys or parameter is unable..
Param
eter
Standard
Control
ST.MV
Heating
and
Cooling
Control
Description
Setting Range
RUN / STOP
Setting Range
ON/OFF
000.0 (OFF)/100.0 (ON)
Control
PID
000.0 to100.0
Control
`00.0 (Cooling ON)
ON/OFF
/000.0 (OFF)/100.0
Control
(Heating ON)
PID
`00.0 (Cooling) to 100.0
Control
(Heating)
© Copyright Reserved Autonics Co., Ltd.
Factory Default
RUN
Factory
Default
000.0
000.0
000.0
000.0
Unit
-
Unit
%

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tk4spTk4lTk4mTk4wTk4h

Table of Contents