6.2.5.3
Current Output Range Settings [PAR3 → O!MA/O@MA]
If the control output is set to current output, you can select upper and lower limit range for
the current output as either 4-20 mA or 0-20 mA.
Parameter
6.3
Temperature Control
6.3.1
Temperature Control Mode [PAR3 → C-MD]
You can choose the type of temperature control method.
Standard
Control
Heating and
Cooling
Control
Setting
Group
PAR3
© Copyright Reserved Autonics Co., Ltd.
Sets OUT1's current output range.
O1.MA
Sets OUT2's current output range.
O2.MA
This parameter is only available on models supporting current output
(OUT1, OUT2).
Setting
PID
ONOF
P.P
P.ON
ON.P
OnON
Paramet
er
Standard
C-MD
Heating and
Description
Heating
PID Control
PID Control
ON/OFF Control
ON/OFF Control
Setting Range
PID / ONOF
Control
Cooling
P.P / P.ON / ON.P / ON.ON
Control
6 Parameter Settings and Functions
Description
Cooling
PID Control
ON/OFF Control
PID Control
ON/OFF Control
PID Control
ON/OFF Control
Factory
Default
PID
Unit
-
P.P
69