Communication Settings; Unit Address Settings [Par4 → Adrs] - Autonics TK4S User Manual

Standard type temp controller tk series
Hide thumbs Also See for TK4S:
Table of Contents

Advertisement

6.6

Communication Settings

Interface
Standards
Max. Connections
Communication
Synchronization
Valid Communication
Distance
BPS (Bits Per Second)
Response Standby
Communication Start Bit
Data Bit
Communication Parity Bit
Communication Stop Bit
Protocol
6.6.1
Unit Address Settings [PAR4 → ADRS]
You can assign individual addresses to data units.
Setting
Group
PAR4
© Copyright Reserved Autonics Co., Ltd.
This feature is used for external higher systems (PC, GP, etc.) to set the controller's
parameters and to monitor the controller. It can also be used to transmit data to
external devices.
No redundant unit addresses may exist along the same communication line. The
communication cable must be a twist pair that supports RS485.
Category
You could modify the parameter (first in, first out) using keys during
communication connection, but this may lead to errors and malfunctions.
Parameter
ADRS
EIA RS485-compliant
31 units (Addresses: 01 through 99)
Two-wire, half duplex
Asynchronous
Max. 800 m
2400, 4800, 9600, 19200, 38400 bps
5 ms to 99 ms
1 bit (fixed)
8 bit (fixed)
None, Even, Odd
1, 2 bit
Modbus Remote Terminal Unit (★
Setting Range
01 to 99
6 Parameter Settings and Functions
Description
1
Character = 11 bit as fixed)
Factory
Default
01
Unit
-
93