6.2.4.3
Initial MV for Manual Control [PAR5 → PR.MV]
If the baseline MV for manual control is configured to PR.MV (Preset Manual MV), you can
set the initial MV for manual control.
Setting
Group
PAR5
6.2.5

Output Settings

6.2.5.1
Control Output (OUT1/OUT2) Selection [PAR3 → OUT1/OUT2]
Setting Group
© Copyright Reserved Autonics Co., Ltd.
Parameter
Standard
Control
PR.MV
Heating
Cooling
Control
When in heating and cooling control mode, a setting between 0.1 and
100.0 will be applied as heating MV and a setting between 0.1 and -
100.0 will be applied as cooling MV.
In case of selecting the Models with current control output, both current and SSR
outputs are available. You can therefore choose the right output type depending on
application environments.
OUT1: Selects OUT1 control output.
OUT2: Selects OUT2 control output.
Parameter
OUT1
PAR3
OUT2
Setting Range
ON/OFF
000.0 (OFF)/100.0
Control
(ON)
PID
000.0 to100.0
Control
-100.0 (Cooling
On)
ON/OFF
/ 000.0
Control
(OFF)/100.0
(Heating ON)
and
-100.0 (Cooling) to
PID
000.0 (OFF)
Control
to 100.0 (Heating)
Setting Range
SSR / CURR
6 Parameter Settings and Functions
Factory
Default
000.0
Factory
Default
SSR
Unit
%
Unit
-
67