6 Parameter Settings and Functions
6.5.3

Communications Parity Bit Settings

Parity bit is a data communication method that adds an additional bit to each character in
transmitted data as an indicator used to verify data loss and corruption. This parameter is
used to enable or disable the parity bit option.
(Communication Setting)
6.5.4

Communication Stop Bit Settings

You can set the number of bits to mark the end of a transmitted data string.
(Communication Setting)
6.5.5

Response Wait Time Settings

Set a standby time to mitigate communication errors when communicating with a slow
master device (PC, PLC, etc.). Once a standby time is set, the controller will respond after
the defined standby time has elapsed.
(Communication Setting)
82
SV (Setting Value)
NONE
EVEN
ODD
Group
Option Setting Group
Setting Value
1
2
Group
Option Setting Group
Group
Option Setting Group
Shorter standby times can cause communication errors in the master
device.
Disables parity bit.
Sets the total bits with signal value of 1 as even numbers.
Sets the total bits with signal value of 1 as odd numbers.
Parameter
Parity Bit
NONE, EVEN, ODD
Sets end of data string to 1 bit.
Sets end of data string to 2 bit.
Parameter
Stop Bit
Parameter
Response Wait
Time
© Copyright Reserved Autonics Co., Ltd.
Description
Factory
Range
Default
NONE
Description
Factory
Range
Default
1, 2
2
Factory
Range
Default
5 ~ 99
20
Unit
-
Unit
-
Unit
ms