Output Settings - Autonics TM Series User Manual

Multi-channel modular temperature controller
Hide thumbs Also See for TM Series:
Table of Contents

Advertisement

※Reverting to power, the control starts with the MV of the power off.
6.2.4.2
Manual control initial MV.
If the baseline MV for manual control is configured to PR.MV (Preset Manual MV), you
can set the initial MV for manual control.
Group
Control
Setting
6.2.5

Output Settings

6.2.5.1
Control Output Settings
If the control output type is a current or SSR output model, control output is supported at
the same time, so the user can choose a suitable output type.
Initial Setting Group
© Copyright Reserved Autonics Co., Ltd.
Preceding Condition
Heating, Cooling, PID
Heating and Cooling,
Group
PID
When in heating and cooling control, a setting between 0.1 and 100.0
applies heating MV, and a setting between 0.1 and -100.0 applies
cooling MV.
Group
The relevant parameter will be activated only if the model is TM2-□□C□
(current or SSR output type).
Parameter
Preset MV
Parameter
Output Type
Current, SSR
6 Parameter Settings and Functions
Factory
Range
Default
0.0 ~ 100.0
-100.0 (Cool) to
0.0 to 100.0
(Heat)
Factory
Range
Default
SSR
Unit
0.0
%
0.0
Unit
-
59