Master Programming Level
SYSTEM SETUP

1=TIMERS

2=NAC
3=RELAYS
System Setup Screen #2
TIMERS
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while
viewing System Setup Screen #2. The following screen will be displayed:
1=PAS DELAY
2=PRE SIGNAL
3=WATERFLOW
1=AC LOSS DELAY
PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds
for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following
display will appear:
RANGE 0-180 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will
indicate the new delay time.
Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of
001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen
#1. The following screen will be displayed:
RANGE 0-180 SECONDS
TIMERS
Timer Screen #1
TIMERS
Timer Screen #2
PAS DELAY
PAS Delay Screen
PRESIGNAL DELAY
Pre-signal Delay Screen
Programming
000
000
000
000
103