GridFminRecT(Hz)
GridFRecT(S)
GridV.Unbal(%)
(2) "3 ON/OFF" menu: Set up the start-up and shut-down control parameters.
Table 5-5 Start-up and turn-off control parameters
Parameter name
PVStartVol(V)
SoftStep(KW/S)
SoftOffOption
OffPStep(KW/S)
IsoResis(KOhm)
GridReStep(KW/S)
(3) "4 PowerContr" menu: relative functions of active, reactive power control
and over-frequency derating, including "ActiveContr(%)", "RePowerContr"
and "FreqDeratCtrl" menus.
1. "ActiveContr(%)" menu: adjust the active power of AC output, the
range is 0~100.0%.
2. "RePowerContr" menu: set up the reactive power control mode,
including 6 submenus: "1. None", "2. Dispatch", "3. Q Set", "4. PF Set", "5.
PF(P) Set" and "6. Q(U) Set".
Recovery threshold value
of Min. grid frequency
Recovery time of grid
frequency protection
Threshold value of grid
voltage unbalance
Description
PV start-up voltage
Soft step
Soft turn off option
Turn off power step
Isolation resistance
Grid fault recovery step
73
{45.00, 47.51, 60.00}
{0, 300.00, 600.00}
{0.1, 2.6, 100}
Setup range (lower limit,
default & upper limit)
{300.0,330.0,400.0}
{0.01,1.00,2.00}
{Ban, Ban,Enable}
{0.01,1.50,2.00}
{10.0,40.0,1000.0}
{0.01,0.04,2.00}