[P29 error]
Are connections of
cable/connector normal?
YES
Is compressor normal?
YES
[H03 error]
Are cablings of power and
current sensor normal?
YES
Check IPDU.
®
Defect
Replace
NO
NO
Is not earthed?
NO
Is not winding shorted?
(Is resistance between windings 0.6 to 1.2 ?)
NO
Is not winding opened?
NO
Check IPDU P.C. board.
®
Defect
Replace
NO
* For RAV-SM563AT-E, SM803AT-E, replace control P.C. board.
YES
YES
YES
* For RAV-SM563AT-E, SM803AT-E,
replace control P.C. board.
– 94 –
Revised : Mar. 2007
Check and correct circuit cabling
such as cabling to compressor.
®
Compressor error
Replace
®
Compressor error
Replace
®
Compressor error
Replace