Toshiba RAV-SM563UT-E Service Manual page 124

Air-conditioner split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

No.
Part name
1. Detachment
Drain pan
NOTE :
Remove the connector by releasing locking
of the housing.
NOTE 1 :
When removing the drain cap, be sure to
prepare a bucket to catch the drained water.
NOTE 2 :
Thermal insulator is adhered to the drain
cap. Be careful not to peel off the insulator.
If the insulator has been peeled, adhere it
with double-face tape, etc. as before.
2. Attachment
Procedure
1) Perform works of items 1 of
ƒ
of
and 1 of
.
2) Remove clamps of the lead wires con-
nected to the following connectors of the
control P .C. board.
CN34
: Float switch (3P: Red)
CN68
: Drain pump (3P: Blue)
CN101 : TC sensor (2P: Black)
CN102 : TCJ sensor (2P: Red)
CN333 : Power supply of fan motor
(5P: White)
CN334 : Position detection of fan motor
(5P: White)
3) Remove screws fixing earth lead wire in
the electric parts box. (Ø4 × 6, 2 pcs.)
4) Remove indoor/outdoor inter-unit cable
and remote controller cable of the
terminal block.
5) Remove screws fixing the electric parts
box. (Ø4 × 10, 5 pcs.)
6) Remove screws fixing the bell mouth.
(Ø4 × 10, 6 pcs.)
7) Remove the drain cap, and drain water
accumulated in the drain pan.
8) Remove screws fixing the drain pan.
(Ø4 × 8, 4 pcs.)
1) Fix the parts, drain cap, drain pan, bell
mouth, and electric parts box succes-
sively to their original positions.
2) Connect connectors, earth lead wire,
indoor/outdoor inter-unit cable, and
remote controller cable which have been
disconnected in the above item 1 as
before.

, 1 of
, 1
– 124 –
Remarks
Screws fixing earth lead wires
S S crews fixing earth lead wires
Drain cap
Drain cap
Screws fixing drain pan
Screws fixing drain pan

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents