Toshiba RAV-SM563UT-E Service Manual page 152

Air-conditioner split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

No.
Part name
Inverter
1) Perform the works in 1 of
assembly
2) Remove connectors which are connected
*(Note 1)
Remove the connectors by releasing lock of
the housing.
3) Remove various lead wires from the
4) Cut off tie lap which fixes various lead
5) Lift up the hook (upper left) with the
* Caution to mount the inverter assembly
Procedure
from the cycle P .C. board to other parts.
CN600: TD sensor (3P: White)
CN601: TO sensor (2P: White)
CN604: TE sensor (2P: White) *(Note 1)
CN605: TS sensor (3P: White) *(Note 1)
CN301: Upper outdoor fan (3P: White)
*(Note 1)
CN300: Detection of upper position
(5P: White)
CN303: Lower outdoor fan (3P: White)
*(Note 1)
CN302: Detection of lower position
(5P: White)
CN500: Case thermo. (2P: Blue)
*(Note 1)
CN700: 4-way valve (3P: Yellow)
*(Note 1)
CN702: PMV (Pulse Motor Valve) coil
(6P: White) *(Note 1)
Relay connector:
Reactor 2 pcs. (2P: White)
Compressor lead: Remove terminal cover
of the compressor, and remove the lead
wire from terminal of the compressor.
holder at upper part of the inverter.
wires to the inverter assembly.
partition plate upward just removing.
Mount the inverter assembly to the partition
plate so that hooks of the heat sink cover
do not come near the partition plate but
also near the fan side.

ƒ
and
.
Inverter assembly
Hooks of heat sink cover
(2 positions)
– 152 –
Remarks
Cycle P.C. board
Inverter assembly
Heat sink cover