Toshiba RAV-SM563UT-E Service Manual page 111

Air-conditioner split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

12-1-3. Monitor Function of Remote Controller Switch
n Call of sensor temperature display
<Contents>
Each sensor temperature of the remote controller, indoor unit, and outdoor unit can become known by calling
the service monitor mode from the remote controller.
<Procedure>
1
CL
TEST
Push
+
buttons simultaneously for 4 seconds or more to call the service monitor mode.
The service monitor goes on, the master indoor unit No. is displayed, and then temperature of the item
00
code
is displayed.
2
Push the temperature setup
sor to be monitored.
The sensor numbers are described below:
Item code
00
01
Indoor
02
unit data
03
04
*1 Only master unit in group control
3
The temperature of indoor units and outdoor unit in a group control can be monitored by
UNIT
pushing
button to select the indoor unit to be monitored.
4
TEST
Pushing
button returns the display to usual display.
/
buttons to select the sensor No. (Item code) of the sen-
SET
DATA
TEMP.
2
TIMER SET
4
FILTER
RESET TEST
SET CL
1
<Operation procedure>
1
2
Data name
Room temp. (control temp.) *1
Room temp. (remote controller)
Room temp. (TA)
Heat exchanger temp. (TCJ)
Heat exchanger temp. (TC)
UNIT No.
R.C.
No.
ON / OFF
FAN
MODE
TIME
SWING/FIX
VENT
UNIT
3
4
Returned to usual display
Item code
60
61
Outdoor
62
unit data
63
64
65
– 111 –
3
Data name
Heat exchanger temp. TE
Outside temp. TO
Discharge temp. TD
Suction temp. TS
Heat sink temp. THS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents