4. Outdoor fan control
W 1
SM56
200
300
SM80
200
300
SM110
250
280
SM140
250
280
1) Cooling fan control
Q
The outdoor fan is controlled by TE, TD, and TO sensors and also revolution frequency of the opera-
tion. The outdoor is controlled by every 1 tap of DC fan control (15 taps).
R
Only during 60 seconds after the operation has started, the fan is fixed with the maximum fan tap
which corresponds to the zone in the following table.
After then the fan is controlled by TE sensor temperature.
S
Considering a case that TE sensor has come out of the holder, the fan is controlled so that revolution
frequency of the fan increases regardless of TE if temperature of TD sensor has risen.
SM56, SM80
SM110, SM110
TE [˚C]
+1 tap/20 seconds
a
b
–1 tap/20 seconds
(The operation frequency differs according to the model type.)
Temp. range
29°C < TO
15 < TO < 29°C
5 < TO < 15°C
0 < TO < 5°C
TO < 0°C
TO error
Allocations of fan tap revolutions [rpm]
W 2
W 3
W 4
W 5
350
410
480
500
350
410
480
500
320
360
410
460
320
360
410
460
a
b
36
32
29
26
rpm hold
Below 30Hz
Min.
Max.
W5
WA
W3
W7
W2
W5
W1
W3
W1
W2
W1
WF
W 6
W 7
W 8
530
560
640
670
530
560
640
670
520
580
640
700
520
580
640
700
Operation with WE
TD [˚C]
85
80
75
65
Above 30 Hz below 45 Hz
Min.
Max.
W7
WC
W5
W9
W4
W7
W3
W5
W2
W4
W1
WF
– 77 –
W 9
W A
W B
W C
700
750
800
840
700
750
840
940
760
860
860
900
760
860
860
900
Operation with
maximum tap in
each zone
Usual fan control
Above 45 Hz
Min.
Max.
W9
WF
W7
WB
W6
W9
W4
W7
W3
W5
W1
WF
W D
W
840
980
930
970