Toshiba RAV-SM563UT-E Service Manual page 35

Air-conditioner split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

RAV-SM563UT-E, RAV-SM562BT-E, RAV-SM562CT-E / RAV-SP562AT-E
Outer diameter of refrigerant pipe
Gas side ØA
Liquid side ØB
12.7mm
6.4mm
Height difference (m)
Outdoor unit
Outdoor unit
at upper side
at lower side
30
15
TS sensor
TD sensor
Rotary compressor
(DA220A2F-20L1)
Accumulator
(1500cc)
Pressure
(MPa)
Pd
Standard
2.71
Cooling
Overload
3.48
Low load
1.92
Standard
2.22
Heating
Overload
3.47
Low load
1.79
4 poles are provided to this compressor.
*
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
TC sensor
* The refrigerating cycle of the indoor units differs according to
the models to be combined. For the refrigerating cycles of the
other indoor units, refer to the corresponding Service Manuals
described in the list on the cover.
Refrigerant pipe
at gas side
Outer dia. ØA
Packed valve
Outer dia. ØA
Strainer
4-way valve
Muffler
(STF-0213Z)
Heat exchangerØ8
Ø25 × L210
1 row 30 stages
Ø25 × L160
FP1.3 flat fin
Pipe surface temperature (°C)
Discharge
Suction
Ps
(TD)
(TS)
1.03
75
15
1.16
81
20
0.74
34
5
0.72
32
6
1.16
81
20
0.25
71
–16
Indoor unit
Air heat exchanger
Section shape
of heat insulator
Outdoor unit
TO sensor
TE
sensor
Indoor heat
Outdoor heat
exchanger
exchanger
(TC)
(TE)
10
38
16
51
2
11
38
2
55
15
30
–18
– 35 –
TCJ
sensor
Refrigerant pipe
at liquid side
Outer dia. ØB
Min.
5m
Packed valve
Outer dia. ØB
Modulating
(PMV)
(CAM-B30YGTF-2)
Strainer
Capillary
Ø3×Ø2×
L530
R410A 1.5 kg
Indoor/Outdoor
Compressor
temp. conditions
Indoor
revolutions per
fan
second (rps)
Indoor
*
43
HIGH
27/19
44
HIGH
32/24
24
LOW
18/15.5
41
HIGH
41
LOW
70
HIGH
Max.
50m
Cooling
Heating
(DB/WB) (°C)
Outdoor
35/–
43/–
–5/–
20/–
7/6
30/–
24/18
15/–
–15/(70%)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents