Toshiba RAV-SM563UT-E Service Manual page 91

Air-conditioner split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

[P22 error]
Are connections of CN301 and
CN300 of P .C. board correct?
Does the fan rotate without trouble
when handling the fan with hands under condition
of removing CN301 and CN300 from P .C. board?
The status that the resistance values
between leads below are 50 to 80 W
for 40 W motor (ICF-140-40) and 25 to 55 W
for 60 W motor (ICF-140-60-1) is normal.
Between
1
(Red lead) and
Between
(White lead) and
2
Between
(Black lead) and
3
of motor winding of connector (CN301)
The status that there is
5k to 20kΩ resistance values between
(Yellow lead) and
1
of motor position detection of
connector (CN300) is normal.
Normal fan motor
(Control or CDB P .C. board)
(Control P .C. board or CDB P .C. board)
NOTE :
However, GND circuit error inside of the motor is rarely detected even if the above check is carried out.
When the circuit does not become normal even if P .C. board has been replaced, replace outdoor fan motor.
Objective P.C. board
Fan motor winding
Motor position detection
YES
YES
2
(White lead)
(Black lead)
3
(Red lead)
1
YES
(Pink lead)
4
YES
RAV-SM563AT-E
RAV-SP562AT-E, SP802AT-E
RAV-SM803AT-E
RAV-SM1103AT-E, SM1403AT-E
Control P.C. board
CN300
CN301
NO
CN301,
NO
CN300 : Motor coil winding
CN301 : Motor position detection
NO
CN301, CN303 : Motor coil winding
CN300, CN302 : Motor position detection
SM110, SM140, SP56, SP80, SP110, SP140
Defective fan motor
Single phase
CDB P.C. board
CN301
CN300
– 91 –
Revised : Mar. 2007
CN303
CN300
RAV-SP1102AT-E, SP1402AT-E
CDB P.C. board
CN301/CN303
CN300/CN302