No.
Item
9
Drain pump control
10
After-heat
elimination
11
Louver control
(For 4-way air
discharge cassette
type only)
Outline of specifications
1) In cooling operation (including Dry operation), the
drain pump is usually operated.
2) If the float switch operates while drain pump
operates, the compressor stops, the drain pump
continues the operation, and a check code is
output.
3) If the float switch operates while drain pump stops,
the compressor stops and the drain pump oper-
ates. If the float switch keeps operating for approx.
4 minutes, a check code is output.
When heating operation stops, the indoor fan oper-
ates with LOW mode for approx. 30 seconds.
1) Louver position setup
• When the louver position is changed, the
position moves necessarily to downward dis-
charge position once to return to the set posi-
tion.
• The louver position can be set up in the follow-
ing operation range.
In cooling/dry operation
• In group twin/triple operation, the louver posi-
tions can be set up collectively or individually.
2) Swing setup
• The swinging position can be moved in the
following operation range.
All modes
• In group twin/triple operation, the swinging
positions can be set up collectively or individu-
ally.
3) When the unit stops or when a warning is output,
the louver automatically moves downward.
4) While the heating operation is ready, the louver
automatically moves upward.
In heating/fan operation
– 66 –
Remarks
Check code [P10]
W arning :
A check code is displayed
on the remote controller,
and the indoor unit stops.
(Excluding [F08] and
[L31])