Toshiba RAV-SM563UT-E Service Manual page 109

Air-conditioner split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

DN
Item
01
Filter sign lighting
0000 : None
time
0002 : 2500H (4-Way/Duct/Ceiling Type)
02
Dirty state of filter
0000 : Standard
03
Central control
0001 : No.1 unit
address
0099 : Unfixed
06
Heating suction temp
0000 : No shift
shift
0002 : +2°C
0F
Cooling only
0000 : Heat pump
10
Type
0001 : SM563/803/1103/1403UT, SP1102UT type
0004 : SM562/802/1102/1402BT type
0007 : SM562/802/1102/1402CT type
11
Indoor unit capacity
0000 : Unfixed
0009 : 56 type
0015 : 110 type
12
Line address
0001 : No.1 unit
13
Indoor unit address
0001 : No.1 unit
14
Group address
0000 : Individual
0002 : Sub of group
19
1E
Temp difference of
0000 : 0 deg
automatic cooling/
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
heating mode
selection COOL →
HEAT, HEAT →COOL
28
Automatic restart of
0000 : None
power failure
2A
Option
2b
Thermo output
0000 : Indoor thermo ON
selection (T10 ƒ )
0001 : Output of outdoor comp-ON receiving
2E
Option
30
Option
31
Option
32
Sensor selection
0000 : Body TA sensor
33
Temperature
0000 : °C (celsius)
indication
40
Option
5d
High ceiling selection
0000 : Standard filter
(Air volume selection)
0001 : Oil guard, Super-long life, Optical regenerative deodorization
0003 : High performance (65%), High performance (90%),
60
Timer set
0000 : Available (Operable)
(Wired remote
controller)
8b
Correction of high
0000 : None
heat feeling
Item No. (DN) table (Selection of function)
Description
0001 : High degree of dirt
to
0064 : No.64 unit
0001 : +1°C
to
0010 : -10°C
0001 : Cooling only
0012 : 80 type
0017 : 140 type
to
0030 : No.30 unit
to
0064 : No.64 unit
0001 : Master of group
to
0010 : 10 deg
0001 : Restart
0001 : Remote controller sensor
0001 : °F (Fahrenheit)
High antibacterial performance (65%)
0001 : Unavailable (Operation prohibited)
0001 : Correction
– 109 –
(Half of standard time)
(Up to recommendation + 6)
(No display of [AUTO] [HEAT])
Revised : Mar. 2007
At shipment
0002 for D.I. and S.D.I.
models
0000 : Standard
0099 : Unfixed
0002 : +2°C
(Floor type 0000: 0°C)
0000 : Shared for cooling/
heating
According to model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
0003 : 3 deg
(Ts±1.5)
0000 : None
0002 : Default
0000: Thermo. ON
0000 : Default
0000 : Default
0000 : Default
0000 : Body sensor
0000 : °C
0003 : Default
0000 : Standard
0000 : Available
0000 : None

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents