No.
Part name
Fan motor
1) Perform the works in 1 of
2) Take off flange nut fixing the fan motor
3) Remove the propeller fan.
4) Remove connector for the fan motor from
5) Take off fixing screws (4 pcs) with sup-
6) When replacing the fan motor at lower
* Cautions in assembling fan motor
• Be sure to mount the propeller fan and the
• Tighten the flange nut with the following
• The same propeller fan and the fan motor
• Tighten the flange nut with the following
• Be sure to mount the motor lead fixed plate
• Be sure that the propeller fan does not
Procedure
with the propeller fan.
• Loosen the flange nut by turning clock-
wise. (When tightening, turn it counter-
clockwise.)
the inverter.
porting the fan motor so that it does not
fall down.
side, remove the motor lead fixed plate
which is fixed to the partition plate with
screw (ST1T Ø4 × 10, 1 pc), pull the fan
motor lead out of the partition plate, and
then remove the fan motor.
<In case of RAV-SP1102AT-E>
fan motor at upper and lower sides be-
cause they are different.
torque.
Upper side: 9.8N·m (100kgf·cm)
Lower side: 4.9N·m (50kgf·cm)
<In case of RAV-SP1402AT-E>
are used at upper and lower sides.
torque.
Upper side: 9.8N·m (100kgf·cm)
Lower side: 9.8N·m (100kgf·cm)
so that the fan motor lead is not caught in.
come to contact with the fan motor lead.

and 1 of
.
Propeller fan
Fan motor connector at upper side
Fan motor connector at lower side
Fan motor
lead
Partition
plate
Motor lead
fixed plate
– 155 –
Remarks
Flange nut
Flange nut
Loosen by
Loosen by
turning clockwise.
turning clockwise
Cycle P.C. board
kwise.
Fan motor

Hide quick links: