7. Troubleshooting guide

This is a basic checklist for your gate automation system. Should you
experience a fault with the system, see if the symptom corresponds to
any given in the list below. For each symptom listed, the probable cause
and action to be taken is given. Terminals and LEDs referred to in the
fault-finders table usually refer to those found on the VECTOR2
controller in the enclosure that is usually mounted on the gate pillar
closest to the Master VECTOR2 operator.
In the event of the symptom not being listed, consult your installer, or
Centurion Systems, for assistance.
Prior to working inside the control card enclosure,
ensure that the mains supply to the system has been
isolated. With the battery connected, the actuator will
remain operational
As this product is used outside of the control of the
manufacturer, Centurion Systems (Pty) Ltd, it cannot be held
responsible for consequential damage as a result of the end
user attempting to maintain the unit without the assistance of
a qualified installer
Symptom
Gate does not
open, or close,
fully, or gate
moves a short
distance and then
stops.
Cause
There is an object
obstructing the
movement of the gate
Anti-crushing device
setting is too
sensitive
Position control
system is malfunc-
tioning
Action
INDICATION: STATUS LED
will be flashing four times
per two seconds and the
LCD will show 'Collision
Detected - Trig to reset'
Clear any obstructions
from the gate.
Disconnect the VECTOR2
from the gate by remov-
ing the pin from the gate
bracket. Check that the
motor operates correctly
without the gate con-
nected. Consult your
installer should there still
be a problem
Check that the cables
from the VECTOR2
actuator are terminated
correctly and making
good contact.
Consult your installer
should there be a problem
page 27
Trouble-
shooting
guide