Specifications - Bosch ICP-EZM2 Installer's Manual

Intrusion control panel
Hide thumbs Also See for ICP-EZM2:
Table of Contents

Advertisement

Easy Series (ICP-EZM2) | Installer Guide | 7.0 Reference Materials
7.8

Specifications

Enclosure
Dimensions (H x W x D):
Construction Material:
Environmental Considerations
Relative Humidity:
Operating Temperature:
Storage Temperature:
Supervised Points
On-board Hardwire:
Programmable Outputs (PO)
On-board:
PO 1 Relay Rating:
PO 2 to PO 4 Rating:
Control Center
Dimensions (H x W x D):
Total Number Supported:
Recommended Mounting Surface:
Minimum Mounting Distance:
Current Draw:
Minimum Wire Length:
Maximum Wire Length:
Data Bus Wire Type Options:
Audio Bus Wire Type Options:
CAT5 Wire Requirements:
Number of...
Users:
Events:
Tokens and Key Fobs:
74
37 cm x 31.8 cm x 8.5 cm (14.5 in. x 12.5 in. x 3.4 in.)
Cold-rolled steel, zinc seal, 0.36 mm thick (20 Ga.)
93% at 32°C ± 2°C (+90°F ± 2°F)
-10°C to +49°C (+14°F to +120°F)
UL: 0°C to +49°C (+32°F to +120°F)
CE: -10°C to +40°C (+14°F to +104°F)
-10°C to +55°C (+14°F to +130°F)
8
Single or dual end-of-line (EOL) tamper point support
Point 1 supports two-wire smoke detectors
All points support four-wire smoke detectors
Enclosure tamper input (does not reduce point capacity)
4
PO 1 only: Configurable relay
PO 2 to PO 4: Configurable solid state
PO 4 only: Internal supervised speaker driver option
Contacts: 2 A with no jumper installed; resistive loads only
Output: 1.2 A with jumper installed; resistive loads only
Operating Voltage: 30 VDC maximum
400 mA current sink
12 cm x 17.7 cm x 2.5 cm (4.7 in. x 7 in. x 1 in.)
4
Non-metallic surface
1.2 m (4 ft) between each control center
110 mA standby; 165 mA alarm
3 m (10 ft)
Total: 400 m (1312 ft) using using 0.8 mm (#22 AWG) wire;
Single run: 100 m (328 ft) using 0.8 mm (#22 AWG) wire
1 four-conductor, power-limited 1.2 mm (#18 AWG) or 0.8 mm (#22 AWG)
wire
At least 0.6 mm (#24 AWG) twisted pair CAT5 wire
UL installations require power-limited wiring.
1 two-conductor or 1 four-conductor, power-limited 1.2 mm (#18 AWG) or 0.8
mm (#22 AWG) wire. Only two conductors are used.
At least 0.6 mm (#24 AWG) twisted pair CAT5 wire
UL installations require power-limited wiring.
Unless using CAT5 cable, audio bus connections require a dedicated wire.
Refer to Section 2.3 Control Center Installation on page 10.
22
User 1: Master user
Users 2 to 21: System users
User 22: Duress user
500 history events, stamped with time and date
One per user (User 22 does not receive a token or key fob)
Bosch Security Systems, Inc. | 5/07 | F01U025147-01