Bosch ICP-EZM2 Installer's Manual page 75

Intrusion control panel
Hide thumbs Also See for ICP-EZM2:
Table of Contents

Advertisement

.
Phone Line
Phone line trouble voltage:
Control Panel Power Requirements
AC Input Line Voltage
Total Alarm Power:
Auxiliary Power:
Current Draw:
Voltage:
Battery:
EZPS Power Supply Requirements (not investigated by UL)
AC Input:
DC Output:
DX2010 Input Expander
Operating Voltage:
Current Draw:
Outputs:
Sensor Loop Terminal Wire Size:
Wire Length:
Operating Temperature:
Relative Humidity:
Sensor Loop Resistance:
Sensor Loop:
Bosch Security Systems, Inc. | 5/07 | F01U025147-01
Easy Series (ICP-EZM2) | Installer Guide | 7.0 Reference Materials
Trouble condition occurs when the phone line voltage is between 1.10 V and 4.75 V
Use a UL Listed 18 V Class 2 transformer (22 VAC, VA 50/60 Hz), or the EZPS
Power Supply (not investigated by UL).
1.4 A (AC power and standby battery; intrusion applications only).
With a 7.0 Ah battery, the following current draws apply to all outputs and devices
connected to the system:
Up to 170 mA for 24 hr for fire and combined fire/burglary applications
Up to 400 mA for 4 hr for UL burglary applications
Up to 1.2 A for other applications (not investigated by UL)
12 VDC, 1.0 A maximum. Includes 110 mA for each control center connected to the
system, and up to 400 mA for the programmable outputs.
85 mA standby; 160 mA alarm with all outputs activated
12 VDC nominal (11.2 VDC to 12.3 VDC)
The control panel stops processing point faults when the voltage drops below
9.5 VDC.
D126 (7 Ah) or D1218 (18 Ah) sealed, lead acid rechargeable
1.7 A maximum recharging current
Low battery condition occurs when battery drops below 12 VDC
If AC power fails and the battery drops below 9.5 VDC, the control panel stops
processing point faults. Disconnect the battery under these conditions.
Maximum auxiliary current to recharge standby battery within 72 hours:
-
12 V, 7 Ah Battery: 400 mA
-
12 V, 18 Ah Battery: 900 mA
AC Input Voltage: 100 VAC to 240 VAC
Line Voltage Frequency: 47 Hz to 63 Hz
Maximum Input Current: 0.5 A
Power Factor: Approximately 0.65 at full load
Nominal Output Voltage under AC line input: 18 VDC
Output Voltage Range under AC line input: 16 VDC to 20 VDC
Continuous Rated Output Current: 1.25 A
Output Current Limit: Approximately 1.75 A to 2.5 A
Periodic and Random Deviation (PARD): Less than 250 mV
8 VDC to 14 VDC
35 mA standby; 135 mA maximum with connected accessories
100 mA, 12 VDC supervised output for accessories
0.8 mm (#22 AWG) to 1.8 mm (#14 AWG)
Control panel to DX2010 (DX2010 auxiliary output not used):
0.8 mm (#22 AWG) = 305 m (1000 ft)
-
1.2 mm (#1.2 mm) = 610 m (2000 ft)
-
Control panel to DX2010 (DX2010 auxiliary output supplying 100 mA):
0.8 mm (#22 AWG) = 30 m (100 ft)
-
1.2 mm (#1.2 mm) = 76 m (250 ft)
-
+0°C to +50°C (+32°F to +122°F)
5% to 85% @ +30°C (+86°F)
60 Ω maximum
Up to eight inputs; input contacts can be normally open (NO) or normally closed
(NC) with appropriate EOL resistors for supervision.
75