Easy Series (ICP-EZM2) | Installer Guide | 2.0 Installation
2.3

Control Center Installation (Step 3)

For complete control center installation instructions, refer to the EZ1 Control Center Installation Guide
(P/N: F01U003737) included with the control center.
To ensure proper RF ID reader operation, mount the control center only on a non-metallic surface.
If you install more than one control center, ensure that there is at least 1.2 m (4 ft) of space between each
control center.
1. Set the address on the control center.
The control panel supports up to four
control centers.
Each control center must have a different
address. Valid addresses are 1 to 4.
The address switch is located on the inside
of the control center.
2. Connect the control center data bus
terminals to the control panel data bus
terminals.
3. Connect the control center audio bus
terminals to the control panel audio bus
terminals.
Twisted pair wiring is recommended for
audio bus connections.
If CAT5 cable is used, refer to the following
CAT5 figure.
10
B G Y R
+ -
Bosch Security Systems, Inc. | 5/07 | F01U025147-01