Specifications; D8024; D10024A; Table 2: D8024 Specifications - Bosch Radionics D8024 Operation And Installation Manual

Fire alarm control panel
Hide thumbs Also See for Radionics D8024:
Table of Contents

Advertisement

D8024/D10024A
Overview
2.1

Specifications

2.1.1

D8024

Operating Voltage
Operating Current
Power Supply
Notification
Appliance Circuits
(Sounder Outputs)
On-board Relays
(dry contacts)
Sensor Circuit
Maximum Devices
Sensor Circuit Protection
Display
Keyboard
Dimensions
(H x W x D)
2.1.2

D10024A

Operating Voltage
Operating Current
Power Supply
Indicating Circuits (Output)
On-board Relays
Sensor Circuit
Maximum Devices
Sensor Current
Sensor Circuit Protection
Display
Keyboard
Printer
Dimensions
(H x W x D)
50616B
120 VAC, 60 Hz
Control: 325 mA
Polling Circuit: 30 mA / circuit + sensor load
24 VDC Nominal @ 3 A
2 programmable, 1 A/ output max.
2.2 kΩ supervised EOL resistor
2 Form "C" contacts rated @ 5 A, 250 VAC max. /relay
Supports 1 or 2 D9067 loop driver modules up to 7,200 ft. (2,195 m) 16
AWG (1.5 mm) per loop. No special wire requirements supports Class
"A" wiring
126 per circuit, 2 circuit max.
Power limited, automatic over current protection
2-line by 40-character back lit liquid crystal display
20 LED fire zone indicators
20 LED zone fault indicators
10 LED system indicators
Membrane w/Snap Dome
Alphanumeric 21-key keypad
15.5 in. x 15.75 in. x 5.5 in.
(39 cm x 40 cm x 14 cm)

Table 2: D8024 Specifications

120 VAC Primary
Control: 325 mA
Polling Circuit: 30 mA/circuit + sensor load
24 VDC Nominal at 3 A
4 Programmable Supervised
1 amp/output max Total Current = 2 A
2 Form "C" contacts rated at 5 A, 250 VAC max. per relay
2-wire analog addressable circuit to operate w/addressable analog
protocols
126 per circuit, 5 circuit max.
150 mA typical
Short circuit protection on-board (without isolators in circuit)
2-line by 40-character back lit liquid crystal display 40 or 80 LED zone
Fire indicators 40 or 80 LED zone Fault indicators 10 LED System
indicators
Membrane with Snap Dome Alphanumeric 21-key keypad
40-character remote (optional)
20 in. x 16 in. x 6.6 in.
(51 cm x 40.6 cm x 16.8 cm)

Table 3: D10024A Specifications

D8024/D10024A Operation and Installation Guide
Page 10
© 2002 Radionics

Advertisement

Table of Contents
loading

This manual is also suitable for:

Radionics d10024a

Table of Contents