A - Auto Part Arm (Default = Disabled)
The system will fully arm if an 'Entry/Exit' zone is activated
during the exit mode and will 'Part Arm 1' if an 'Entry/Exit'
zone is not activated during the exit mode.
!
To activate an Entry/Exit zone for this facility it is
sufficient for the zone to switch from active to
healthy (closing of the door only).
S - Part Arm Silent (Default = Disabled)
The system will always Part Arm silently.
R - Remote Arm/Disarm (Default = Enabled)
The system can be armed and disarmed remotely using
the Wintex UDL software and a Digicom or ComGSM.
T - Time Arm CT1 (Default = Disabled)
The system will automatically arm using Control timer 1.
E - Alarms Eng Reset (Default = Disabled)
The system can be programmed for Engineer or User reset
following
an
Intruder
'Alms Eng Reset' the system will respond as follows:
A normal Intruder alarm can only be reset using an
Engineer code
If 'Anti-code Reset' is enabled (option A) the system can
also be reset using the Anti-code
C - Confirmed Reset (Default = Enabled)
The system can be programmed for Engineer or User reset
following a Confirmed alarm, if programmed as 'Confirmed
Reset' the system will respond as follows:
A confirmed Alarm can only be reset using an Engineer
code
If 'Anti-code Reset' is enabled (option A) the system can
also be reset using the Anti-code
T - Tamper Eng Reset (Default = Enabled)
The system can be programmed for Engineer or User reset
following a Tamper alarm (when the system is unarmed), if
programmed as 'Tamper Eng Reset' the system will
respond as follows:
A Tamper Alarm can only be reset using an Engineer code
If 'Anti-code Reset' is enabled (option A) the assigned
areas can also be reset using the Anti-code
A - Anti-code Reset (Default = Enabled)
The system can be programmed for Anti-code Reset
following an Intruder or Tamper alarm, if programmed as
'Anticode Reset' the system will respond as follows:
An Alarm condition can be reset using the Anti-code as
well as an Engineer code
!
The system can only be programmed for 'Anti-code
Reset' if it is also programmed as 'Alarms Eng Reset'.
INS248
alarm,
if
programmed

Options 2

L - Arm With L/Fault (Default = Enabled)
The system can be armed with a line fault present.
A - Arm with AC Fail (Default = Enabled)
The system can be armed with a mains fault present.
P - Part Arm Coms (Default = Disabled)
When 'Part Arm Coms' is enabled the system will respond as
follows:
When the system is part armed and an Intruder alarm
occurs, Intruder alarm events are reported to the Alarm
Receiving Centre after any programmed 'Coms Delay' has
expired
F - Unarm Fire Coms (Default = Disabled)
When 'Unarm Fire Coms' is enabled, Fire alarm events will
be reported to the Alarm Receiving Centre whilst the
system is disarmed
!
Fire alarm events are always reported to the Alarm
Receiving Centre when the system is armed
as
regardless of whether this option is enabled or not.
T - Unarm Tamp. Coms (Default = Disabled)
When 'Unarm Tamp Coms' is enabled, 24Hr and Tamper
alarm events (for that area) will be reported to the Alarm
Receiving Centre whilst the system is disarmed
!
24Hr and Tamper alarm events are always reported
to the Alarm Receiving Centre when the system is
armed regardless of whether this option is enabled
or not.
L - Log Part Omits (Default = Disabled)
When enabled, zones that have been omitted during a part
arm are logged in the event log.
I Confirm in Entry (Default = Disabled)
When 'Confirm in Entry' is enabled the system will respond
as follows:
Once the entry timer is started if two or more zones are
activated a Confirmed alarm will occur, and will be reported to
the Alarm Receiving Centre
!
To comply with DD 243:2002, this option must
NEVER be enabled, thus preventing Confirmed
Alarms from being reported to the Alarm Receiving
Centre during the entry mode.
A - Conf. after Entry (Default = Disabled)
When 'Conf. After Entry' is enabled the system will respond
as follows:
Once the entry timer expires if two or more zones (not on the
entry route) are activated a Confirmed alarm will occur, and
will be reported to the Alarm Receiving Centre
!
If a Portable ACE i.e. Electronic Keyswitch, Key fob,
Tag, Swipe Card etc. is used to disarm the system, it
is permissible for the Confirmed Intruder Alarm
signal to be re-enabled after the entry delay has
expired. In this case, this option CAN be enabled.