Output Group - Alarm

Select an output type from the following options:
00 - Alarm
This output type activates when a general alarm condition
occurs, and deactivates when the alarm is cancelled.
01 - Guard Alarm
This output type activates when a zone programmed as
'Guard' causes an Intruder alarm and deactivates when the
alarm is cancelled.
02 - Guard Access Alarm
This output type activates when a zone programmed as
'Guard Access' causes an Intruder alarm and deactivates
when the alarm is cancelled.
03 - Entry Alarm
This output type activates when a zone programmed as
'Entry/Exit 1 or 2' causes an Intruder alarm and deactivates
when the alarm is cancelled.
04 - Confirmed Alarm
If the system is already in alarm, this output type activates
when a different zone (not on the entry route) is activated and
deactivates at the end of the 'Confirmation' time, when a code
is entered within the 'Abort' time or when the alarm is reset.
05 - 24Hr Audible
This output type activates when a zone programmed as
'24Hr Audible' causes an Internal alarm or Intruder alarm
and deactivates when the alarm is cancelled.
06 - Trouble
This output type activates when a zone programmed as
'Trouble' causes an alarm and deactivates when the alarm
is cancelled.
07 - 24Hr Gas
This output type activates when a zone programmed as
'24Hr Gas' causes a Silent alarm or Intruder alarm and
deactivates when the alarm is cancelled.
08 - PA Alarm
This output type activates when any type of 'PA alarm' i.e.
PA audible, PA silent or Duress causes a PA alarm and
deactivates when the alarm is cancelled.
09 - PA Silent
This output type activates when a zone programmed as
'PA Silent' or a keypad PA (1 & 3) causes a silent PA alarm
and deactivates when the alarm is cancelled.
10 - Duress
This output type activates when a User code with the
'Duress' attribute causes a silent PA alarm and deactivates
when the alarm is cancelled..
11 - Fire Alarm
This output type activates when a zone programmed as
'Fire' or a keypad Fire (4 & 6) causes a Fire alarm and
deactivates when the alarm is cancelled.
INS248
Programming the Control Panel
12 - Medical
This output type activates when a zone programmed as
'Medical' or a keypad Medical (7 & 9) causes a Medical alarm
and deactivates when the alarm is cancelled.
13 - Auxiliary Alarm
This output type activates when a zone programmed as
'Auxiliary' causes a Silent alarm and deactivates when the
alarm is cancelled.
14 - Tamper Alarm
This output type activates when a Tamper alarm is
generated and deactivates when the alarm is cancelled.
15 - Alarm Abort
This output type activates when a User code is entered to
cancel the alarm (within the 'Abort Delay' period and
deactivates after 10 seconds.
16 - Ready
This output type activates when all zones are secure and
deactivates when any zone is active.
17 - Entry Mode
This output type activates when the entry mode is started
and deactivates when the entry mode finishes.
18 - 2
nd
Entry Mode
This output type activates when the 2
and deactivates when the 2
19 - Exit Mode
This output type activates when the exit mode is started and
deactivates when the exit mode finishes.
20 - Entry/Exit Mode
This output type activates when the entry or exit mode is
started and deactivates when the entry or exit mode finishes.
21 - Armed
This output type activates when the system is armed and
deactivates when the system is disarmed.
22 - Full Armed
This output type activates when the system is fully armed
and deactivates when the system is not fully armed.
23 - Part Armed
This output type activates when the system is part armed
and deactivates when the system is not part armed.
24 - Force Arm
This output type activates when there is at least one zone
with the 'Force Omit' attribute assigned to it, and
deactivates when there are no zones with the 'Auto Omit'
attribute assigned to it.
25 - Force Arming
This output type activates when the system has been
forced to arm with zones active, and deactivates when the
zone is reinstated.
26 - Arm Failed
This output type activates when the system fails to arm
because a zone is in fault, and deactivates when the fault
is reset.
nd
entry timer starts
nd
entry timer expires.