The Programming Menu
15 - Coms Failed
This output type activates when the plug-on digimodem fails
to report to the Alarm Receiving Centre (after 3 dialling
attempts), and deactivates the next time the digimodem
successfully reports to the Alarm Receiving Centre.
16 - Coms Successful
This output type activates when the plug-on digimodem
successfully reports to the Alarm Receiving Centre and
deactivates the next time the digimodem is triggered.
17 - Coms Active
This output type activates when the plug-on digimodem is
triggered and deactivates when the digimodem shuts down.
18 - UDL Lockout
This output type activates when an attempt is made to
upload/download with incorrect site details more than
three times and deactivates after 4 hours or after a valid
User code is entered.
19 - UDL Call Active
This output type activates when an upload/download is
started and deactivates when the upload/download finishes.
20 - UDL Enabled
This output type activates when 'Enable UDL/Engineer' is
enabled and deactivates when 'Enable UDL/Engineer' is
disabled.
21 - Custom Output
This output type activates when 'PGM 5 OR 6 AND 7 AND 8'
activate and deactivates when 'any one of the same PGM
outputs deactivate (see page 59 for details).
22 - Activity Fault
This output type activates whenever a zone with the
'Activity' attribute has not activated and deactivates when
the zone activates.
23 - No Battery
This output type activates for 1 minute if the engineer logs off
the control panel and there is no battery fitted.
24 - Control Timer 1
This output type operates when 'Control Timer 1' activates
and deactivates when 'Control Timer 1' deactivates.
25 - Control Timer 2
This output type operates when 'Control Timer 2' activates
and deactivates when 'Control Timer 2' deactivates.
26 - Control Timer 3
This output type operates when 'Control Timer 3' activates
and deactivates when 'Control Timer 3' deactivates.
27 - Control Timer 4
This output type operates when 'Control Timer 4' activates
and deactivates when 'Control Timer 4' deactivates.
28 - Com Port 1 Fault
This output type activates when whatever is connected to
Com Port 1 stops communicating with the control panel
and deactivates when communication starts again.
56
29 - Com Port 2 Fault
This output type activates when whatever is connected to
Com Port 2 stops communicating with the control panel
and deactivates when communication starts again.
30 - Code Accepted
This output type activates for 5 seconds whenever a User
code is entered.
31 - Prox TAG Accepted
This output type activates for 5 seconds whenever a
Proximity TAG is presented.
32 - Radio Jamming
This output type activates whenever the wireless radio
receiver detects a jamming signal and deactivates when
the jamming signal is removed.
33 - Detector Test
This output type is activated via Wintex to initiate a
diagnostics check on an PD6662: 2004/EN 50131-1 Grade
3 detector and deactivates after 10 seconds.
34 - ATS Remote Test
This output type conforms to the BSIA Form 175
Specification. When a Line Fault is not present it can be
activated remotely by Wintex, or by using the 'Start Test
Call' option on the control panel to initiate a test on ATE
equipment that have an ATS test input. NOTE: Only the
RedCare Line Fault and Control panel Line Fault inputs can
be used with the output type.
35 - No ATS Available
This output type activates when no signalling paths are
available for the Alarm Transmission System (ATS) and
deactivates when one or more paths become available.
36 - CIE Fault
This output type activates when a fault occurs on the CIE
and deactivates when the fault is cleared.
37 - PSU Fuse Blown
This output type activates when the Auxiliary input type
'PSU Monitor' detects a 12V failure and deactivates when
the fault is reset.
38 - PSU Battery Flt
This output type activates when the Auxiliary input type
'PSU Monitor' detects a battery fault and deactivates when
the fault is reset.
39 - iD Loop Shorted
This output type activates when the 24iXD detects a short
circuit on the iD loop and deactivates when the fault is
reset
40 – Radioplus Tamper
This output type activates when the intelligent receiver
detects a lid tamper.
41 – GSM No Signal
This output type activates when a GSM device losses the
network signal.