Zone Connections - Texecom Premier 24 Installation Manual

Texecom premier 24 installation manual
Hide thumbs Also See for Premier 24:
Table of Contents

Advertisement

Premier 24 Installation Manual

Zone Connections

Any zones that are not being used must be linked out or
programmed as 'Not Used' (see page 34 for details).
Normally Open or Normally Closed
Use this wiring configuration when connecting normally closed
or normally open detection devices to the zone using 2-Wires.
Z1
Z1
1 Normally
2 Normally
Open Contact
Closed Contact
!
When using this configuration the tampers must be
wired to the Aux tamper input (see page 22 for details).
Double Pole
Use this wiring configuration when connecting normally closed
detection devices to the zone using 4-Wires.
T
A
Zone 1
1 Normally
Closed Contact
!
When using this configuration, no more than 10
detectors can be connected to each zone.
When wiring double pole (4-wires) to a keypad or
zone expander, the wiring configuration must always
be programmed as 'Double Pole/EOL'.
INS248
Z1
Z1
1 Normally
2 Normally
Open Contact
Open Contact
A
T
Zone 1
2 Normally
Closed Contacts
End Of Line
Use this wiring configuration when connecting normally
closed detection devices to the zone using 2-Wires. Zone
wiring should be programmed as Double Pole/EOL.
A
T
Zone 1
Alarm
Alarm
Tamper
E.O.L
2k2W
Alarm
1 Normally
Closed Device
Closed Devices
!
When using this configuration, no more than 3
detectors can be connected to each zone.
Installation
A
T
Zone 1
Alarm Contact Resistor = 4K7
Tamper
EOL Resistor = 2K2
Tamper
E.O.L
2k2W
2 Normally
21